Check your furnace for ventilation pipes that go outside. Furnaces vented to the outdoors do not require indoor combustion air since they pull their combustion air from outside the house.
Locate the manual for your furnace to determine the BTU per hour rating. Check the furnace itself for a paper tag with this information if the manual is unavailable.
Multiply the BTU-per-hour rating by 50, then divide that number by 1,000 to determine the cubic footage of combustion air required for your furnace in a totally open space. Determine the available cubic footage of combustion air by multiplying the length, width and height of the open-basement area.
Enclosed furnaces generally require two openings in the enclosure no smaller than 100 square inches each. Calculate your enclosed furnace's needs by dividing the BTU-per-hour rating by 1,000. Install an upper and lower vent in the structure equal to or greater than this number in surface area. If you will be enclosing the furnace during your remodel, use these figures to determine your ventilation needs.